Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZW32-12 Series outdoor high voltage vacuum circuit breaker is rated voltage 12kV, three phase AC 50Hz outdoor distribution equipment. It is mainly used to breaking closing power system load current, overload current and short-circuit current. Applicable to substations and power distribution in industrial and mining enterprises for protection and control purposes, and frequent operation place for rural power.
The circuit breaker small size, light weight, anti-condensation, maintenance and so on. Adapt to adverse weather conditions, and to teach filthy environment.
Service environment
a) Air temperature: Maximum temperature: +85ºC; Minimum temperature:-45ºC
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude:2500mor more higher.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
No.
|
Item
|
Unit
|
Data
|
1
|
Rated voltage
|
KV
|
12
|
2
|
Rated frequency
|
HZ
|
50
|
3
|
Rated current
|
A
|
630
|
4
|
Rated short circuit breaking current
|
KA
|
20
|
5
|
Rated peak withstand current
|
KA
|
50
|
6
|
Rated short-circuit withstand current
|
KA
|
20
|
7
|
Rated short circuit closing current(peak)
|
KA
|
50
|
8
|
Mechanical life
|
Times
|
10000
|
9
|
Rated short-circuit breaking current breaking times
|
Times
|
30
|
10
|
Power frequency withstand voltage(1 min): ( wet)(dryphase to phase, to earth/Between open contacts
|
KV
|
42/48
|
11
|
Power frequency withstand voltage(1 min): ( wet)(dryphase to phase, to earth/Between open contacts
|
KV
|
75/85
|
12
|
Secondary circuit Imin power frequency withstand voltage
|
KV
|
2
|